NIBE Heat Pump Error Codes

Type the alarm number (for example 220) or a keyword like pressure, sensor or inverter to find your code, then expand the row for checks and next steps.

Info Normal operation, for information only Warning Reduced performance – investigate soon Critical Heat pump protected / stopped – urgent

Description: The BT3 sensor (incoming/flow water sensor) is showing an open or short circuit.

Likely causes: Damaged sensor, loose plug, broken cable, or faulty control board input.

Checks you can do:

  • Power-cycle the heat pump and see if the alarm returns.
  • Visually check the BT3 sensor wiring and plug at the unit (no visible damage, firmly connected).
  • Check for recent work near the pipe sensor that might have disturbed the cable.

Call an engineer if: The alarm reappears after reset or you can see damaged sensor cabling.

Operation: Heating may be limited or blocked until the sensor fault is cleared.

Description: The BT12 sensor (outgoing/return water) is not giving a valid reading.

Checks you can do:

  • Reset the alarm from the controller.
  • Check BT12 wiring and plug for damage or loose connection.

Call an engineer if: The alarm returns or you suspect damage to the sensor or control board.

Operation: Heat pump may run in a protective mode or stop heating.

Description: The BT15 sensor that monitors the refrigerant/pipe temperature is faulty or not connected.

Checks you can do:

  • Try a reset from the alarm menu.
  • Listen for abnormal noises; leave the outdoor unit covers in place.

Call an engineer: This sensor sits inside the refrigerant section; service access is required.

Operation: Compressor will usually be blocked until the sensor issue is fixed.

Description: The flow water leaving the condenser has reached the maximum permitted temperature, so the unit stops or ramps down to protect itself.

Common causes: Low system flow, closed or partially closed valves, dirty strainers/filters, undersized radiators, or an overly steep heat curve.

Checks you can do:

  • Confirm all isolation valves around the heat pump and cylinder coil are open.
  • Check system pressure is around the installer’s recommended value (often ~1.0–1.5 bar when cold).
  • Bleed obvious air from radiators and any air vents on the system.
  • If safe to do so, clean any user-serviceable strainers/filters your installer has shown you.

Call an engineer if: The alarm reoccurs after basic flow/pressure checks or pressure drops repeatedly.

Operation: Compressor is temporarily blocked until conditions are safe.

Description: The return water entering the condenser has reached its maximum allowed temperature.

Checks you can do: Same as for alarm 162 – check valves, pressure, air in the system, and filters.

Call an engineer if: Alarms 162/163 keep coming back or radiators/underfloor loops don’t heat evenly.

Operation: Compressor may be blocked until temperatures fall.

Description: The pressure sensor on the heating circuit has detected pressure below the minimum set level.

Checks you can do:

  • Read the system pressure gauge – typically the target is around 1.0–1.5 bar when cold (check your installer’s label).
  • If trained to do so, top up the system via the filling loop to the labelled pressure.
  • Inspect for obvious leaks on radiators, valves and safety discharge pipes.

Call an engineer if: Pressure keeps dropping, you see leaks, or you’re unsure how to safely top up.

Operation: Heat pump may stop to protect itself from running dry.

Description: The heat pump has temporarily reversed to defrost the outdoor coil. Heating is reduced for a few minutes while ice is melted.

Checks you can do:

  • Make sure the outdoor unit has good drainage so meltwater can run away freely.
  • Keep snow and debris clear of the base and air inlet/outlet grilles.

Call an engineer if: The unit spends long periods defrosting and never seems to catch up, or you see heavy ice build-up that doesn’t clear.

Operation: Normal – the message clears automatically once defrost is finished.

Description: The controller has detected conditions consistent with a blocked system filter and has raised a filter alarm.

Checks you can do:

  • If you’ve been shown how, isolate and clean the system filters/strainers.
  • Bleed air from radiators and manifolds.

Call an engineer if: You’re not comfortable cleaning filters, or the alarm returns quickly.

Operation: Heat output may be reduced; persistent filter alarms can lead to high-pressure shut-downs (e.g. alarm 220).

Description: The high-pressure protection has tripped repeatedly. The heat pump shuts down to prevent damage.

Very common causes:

  • Low system water pressure.
  • Closed or partially closed isolation valves or zone valves.
  • Blocked or dirty strainers/filters in the heat pump or system.
  • Failed or seized circulation/charge pump.
  • Badly balanced or undersized heating emitters causing very low flow.

Checks you can do:

  • Verify system pressure and top up to the installer’s marked value if you know how.
  • Ensure all isolation and zone valves that should be open are fully open.
  • Bleed obvious air from radiators and manifolds.
  • Clean any user-serviceable strainers your installer has identified.
  • Reset the alarm and observe whether it returns quickly.

Call an engineer urgently if: The alarm comes back after basic checks, or you suspect pump failure or heavy system sludge.

Operation: Compressor is blocked until the fault is cleared and alarm reset.

Description: The low-pressure switch or sensor has triggered. This is a refrigerant-side issue.

Possible causes: Refrigerant leak, restriction in the circuit, or very low outdoor air temperature combined with other issues.

User actions:

  • Check outdoor coil and fan are not blocked by leaves, snow or debris.
  • Reset once; do not keep repeatedly resetting.

Call an F-gas engineer: Low-pressure faults are usually refrigerant related and must be investigated professionally.

Operation: Compressor is blocked until an engineer clears the alarm.

Description: The indoor module (SMO/VVM etc.) cannot communicate with the outdoor unit, so the compressor is blocked.

Checks you can do:

  • Confirm power is present to the outdoor unit (MCB on, no tripped breaker).
  • Check any visible communication cable plugs at the indoor module haven’t been disturbed.
  • Power off both indoor and outdoor units at isolators for a few minutes, then power back on.

Call an engineer if: The alarm returns; there may be a wiring, board or communication issue.

Operation: Compressor blocked until communication is restored.

Description: The outdoor fan has stopped or is drawing abnormal current, so the controller blocks the compressor.

Checks you can do (with power off):

  • Visually check for objects stuck in the fan guard (branches, bags, ice).
  • Do not remove covers or try to force the fan – this is engineer work.

Call an engineer: If nothing obvious is blocking the fan, there may be a motor or control fault.

Operation: Compressor blocked until the fan fault is resolved.

Description: The controller has detected abnormal conditions between flow and return, often pointing to low flow or a blocked circuit.

Checks you can do:

  • Check system pressure, valves and filters as for alarm 220.
  • Ensure all key heating zones are open so water can circulate.

Call an engineer if: The alarm persists or appears alongside 162/163/220.

Operation: Depending on model, compressor may be limited or blocked.

Description: A sensor fault has been detected in the outdoor unit (exact sensor is shown in the detailed alarm info or service menu).

User actions: Reset once; beyond that, sensor diagnosis is engineer-level work.

Call an engineer: If the alarm returns or you see several sensor alarms at once.

Description: The outdoor unit reports a problem completing defrost, often linked to sensors or refrigerant conditions.

Checks you can do: Keep the outdoor unit clear of snow/ice buildup and ensure drainage is not blocked.

Call an engineer: Repeated defrost faults need investigation of sensors, charge and expansion device.

Description: The compressor has tripped three times in a row shortly after starting, so the controller blocks it temporarily.

Possible causes: System flow issues, high-pressure trips, incorrect settings, or inverter problems.

Checks you can do: Review any associated alarms (162, 220 etc.), then follow their guidance.

Call an engineer: If 229 appears frequently – it’s usually a symptom of another underlying fault.

Description: The hot-gas/discharge temperature has remained above its limit and the compressor is blocked.

User checks: Same as for high-pressure alarms – confirm good system flow and clean filters.

Call an engineer: Persistent hot-gas alarms can indicate charge or expansion-valve issues.

Description: The heat pump has detected that the three-phase supply is in the wrong order. The compressor is blocked to prevent damage.

User action: Do not attempt to swap phases yourself. Contact the installer or electrician.

Description: The evaporating temperature is too low, often due to refrigerant charge or expansion issues.

User action: Keep the coil clear of snow/ice; then call an F-gas engineer.

Description: The display unit has lost communication with the base card; the compressor and charge pump usually stop.

User actions: Try a full power cycle at the isolators; if the alarm returns, contact an installer.

Description: In multi-unit systems, the master heat pump has lost communication with a slave.

User actions: Check power supplies and visible comms cables; then contact the installer if alarms persist.

Description: The controller reports a general communication problem, often between the indoor board and an accessory or inverter.

User actions: Power cycle; if it recurs, engineer investigation is needed.

Description: The heat exchanger has overheated and the inverter/controls have stopped the compressor.

User checks: Same as for alarm 220 – focus on water flow and filters.

Description: The inverter module has reported an over-temperature condition on its power electronics.

User actions: Ensure vents around the unit are clear and the area is well-ventilated; then call an engineer.

Description: The inverter drive has logged a permanent or repeated error. The detailed sub-code is usually visible in the alarm log and service manual.

User action: Do not repeatedly reset; contact an installer or NIBE service partner for inverter diagnostics.

Description: The controller has detected a mismatch or lost contact with the outdoor unit – commonly after a short power interruption.

Checks you can do:

  • Confirm outdoor unit isolator and breakers are on.
  • Power cycle both indoor and outdoor units if safe to do so.

Call an engineer: If the alarm persists there may be firmware, configuration or hardware compatibility issues.

No error codes match your search. Try a shorter term (for example, just the number like 220 or a single word like pressure).