Severity: High

Description: The inverter power module temperature is too high and the unit has shut down to protect the electronics.

Checks:

  • Check that the outdoor unit has adequate ventilation and is not obstructed.
  • Inspect heat sinks and the inverter area for dust or debris.
  • Verify any fans that cool the electronics are running correctly.

Actions:

  • Restore airflow and clean components as needed.
  • If the error persists, have an engineer test the inverter module and main PCB.

Severity: High

Description: Insufficient water flow has been detected several times and the unit has locked out to protect the system.

Checks:

  • Confirm system water pressure is within the recommended range (typically above 1 bar when cold).
  • Check that all isolation valves are open and strainers/filters are not blocked.
  • Verify the circulation pump is running and properly powered.

Actions:

  • Bleed air from the system and clean strainers/filters.
  • If flow cannot be restored, contact your installer to investigate pipework or pump sizing.

Severity: Medium

Description: On three-phase models the incoming supply phase order is incorrect or has changed.

Checks:

  • Confirm the unit is a three-phase model.
  • Check the phase sequence at the isolator with a suitable tester.
  • Confirm no recent changes have been made to the supply wiring.

Actions:

  • Have a qualified electrician correct the phase order.
  • Do not swap phases yourself unless you are suitably qualified.

Severity: Medium

Description: Loss of communication between the hydronic module main control board and the wired controller / user interface.

Checks:

  • Check the communication cable is securely connected at both ends.
  • Inspect the cable for damage, joints or crushed sections.
  • Power-cycle the system to see if communication is restored.

Actions:

  • If the fault returns, have an engineer test the controller cable.
  • Replace the controller or PCB if communication cannot be re-established.

Severity: Medium

Description: Fault detected on the backup electric heater water outlet temperature sensor.

Checks:

  • Inspect the sensor and wiring at the backup heater outlet.
  • Check connectors for corrosion or loose contacts.
  • Measure sensor resistance and compare with manufacturer values.

Actions:

  • Replace the faulty sensor.
  • If a new sensor does not clear the error, the control board may need replacement.

Severity: Medium

Description: Fault on the domestic hot water tank temperature sensor.

Checks:

  • Check the DHW tank sensor position and ensure it is properly inserted in its pocket.
  • Inspect the sensor cable and connector for damage.
  • Measure sensor resistance at the PCB terminals.

Actions:

  • Re-seat or replace the tank sensor as required.
  • If wiring and sensor are OK, have the PCB checked by an engineer.

Severity: Medium

Description: Fault on the refrigerant outlet temperature sensor of the outdoor heat exchanger.

Checks:

  • Check the sensor is firmly clipped to the coil or pipe.
  • Inspect wiring for damage or disconnection at the outdoor PCB.
  • Measure sensor resistance and compare to the temperature table.

Actions:

  • Replace the sensor if readings are out of range or intermittent.
  • If the error persists, the outdoor PCB may be faulty.

Severity: Medium

Description: Fault on the outdoor ambient air temperature sensor.

Checks:

  • Confirm the sensor is located correctly and not influenced by exhaust air or direct sunlight.
  • Inspect the cable and connector at the outdoor PCB.
  • Measure sensor resistance versus ambient temperature.

Actions:

  • Replace the ambient sensor if readings are incorrect.
  • Check the PCB input if a new sensor does not resolve the issue.

Severity: Medium

Description: Fault on the upper temperature sensor of the buffer / balance tank.

Checks:

  • Verify sensor insertion depth and physical mounting on the tank.
  • Inspect wiring back to the hydronic box PCB.
  • Measure sensor resistance and compare to specified values.

Actions:

  • Reposition or replace the tank sensor.
  • If wiring and sensor test good, have the control board assessed.

Severity: High

Description: The flow switch has detected insufficient water flow during operation.

Checks:

  • Check system pressure, valves and strainers.
  • Confirm the circulation pump is running and correctly vented.
  • Look for airlocks or recently closed valves/radiators.

Actions:

  • Restore correct flow and reset the unit.
  • If E8 recurs frequently, have the hydraulic design and pump selection reviewed.

Severity: Medium

Description: Fault on the compressor suction pipe temperature sensor.

Checks:

  • Inspect the sensor mounting on the suction line for good contact and insulation.
  • Check wiring between the sensor and outdoor PCB.
  • Measure sensor resistance at a known temperature.

Actions:

  • Replace the suction sensor if out of specification.
  • If the problem remains, further diagnosis of the PCB is required.

Severity: Medium

Description: Fault on the compressor discharge pipe temperature sensor.

Checks:

  • Inspect sensor contact and insulation on the discharge line.
  • Check for damaged or loose wiring.
  • Measure sensor resistance and compare to the temperature table.

Actions:

  • Replace the sensor if necessary.
  • If error persists with a good sensor, suspect a PCB input fault.

Severity: Medium

Description: Fault on the solar panel or auxiliary temperature sensor (where fitted).

Checks:

  • Verify the system actually uses the solar/aux sensor – some installations leave it unused.
  • Check sensor wiring and terminals.
  • Measure sensor resistance if the sensor is connected.

Actions:

  • Disable unused sensor inputs in settings if supported, or fit a dummy sensor where required.
  • Replace the sensor if the circuit is in use and readings are incorrect.

Severity: Medium

Description: Fault on the lower temperature sensor of the buffer / balance tank.

Checks:

  • Check sensor mounting at the lower position on the tank.
  • Inspect the cable for damage or loose connectors.
  • Measure sensor resistance and compare to specification.

Actions:

  • Re-seat or replace the tank sensor.
  • If the fault remains, the sensor input on the PCB may be damaged.

Severity: Medium

Description: Fault on the water side heat exchanger inlet water temperature sensor.

Checks:

  • Confirm the sensor is correctly installed on the inlet pipe.
  • Inspect wiring between sensor and hydronic PCB.
  • Measure sensor resistance at the PCB terminals.

Actions:

  • Replace the inlet sensor if defective.
  • Have the control board checked if a new sensor does not clear the error.

Severity: High

Description: The controller memory (EEPROM) in the hydronic box is not being read correctly.

Checks:

  • Power the unit off completely for several minutes and restart.
  • Check all low-voltage connections on the hydronic PCB.
  • Confirm supply voltage is stable and within limits.

Actions:

  • If the error returns, the hydronic PCB will usually need to be repaired or replaced.
  • Contact the manufacturer support channel or your installer.

Severity: High

Description: The inverter DC bus voltage has dropped below the safe operating threshold.

Checks:

  • Check mains voltage is within the specified range under load.
  • Inspect mains terminals and internal power wiring for loose connections.
  • Look for signs of damage or overheating around the inverter module.

Actions:

  • Have an electrician check the supply and breaker sizing.
  • If supply is sound, the inverter or main PCB may require replacement.

Severity: Medium

Description: Loss of communication between the outdoor unit main control and the hydronic module.

Checks:

  • Check the interconnecting communication cable (P/Q or equivalent) for continuity.
  • Ensure polarity is correct on communication terminals.
  • Inspect for water ingress or corrosion at terminals.

Actions:

  • Repair or replace damaged cabling.
  • If wiring is sound, an engineer may need to replace one of the PCBs.

Severity: High

Description: The outdoor main controller cannot reliably communicate with the inverter drive module.

Checks:

  • Inspect the harness between the main PCB and inverter module.
  • Check for LED status indicators on both boards per the service manual.
  • Verify supply voltages to the inverter module.

Actions:

  • Reseat or replace the harness as needed.
  • If the error persists, either the inverter module or outdoor main PCB may be faulty.

Severity: Medium

Description: Fault on the refrigerant outlet (liquid line) sensor of the water side heat exchanger.

Checks:

  • Check the sensor clamp and insulation on the liquid line.
  • Inspect wiring back to the outdoor PCB.
  • Measure sensor resistance against the temperature chart.

Actions:

  • Replace the sensor if readings are incorrect.
  • If still faulty, investigate the PCB input.

Severity: Medium

Description: Fault on the refrigerant inlet (gas line) sensor of the water side heat exchanger.

Checks:

  • Inspect sensor mounting on the suction/gas line.
  • Check cable and connector condition.
  • Measure sensor resistance at a known temperature.

Actions:

  • Install a new sensor if defective.
  • If a good sensor does not clear the code, suspect the controller.

Severity: High

Description: Inverter protection (such as L0/L1) has occurred multiple times in a defined period.

Checks:

  • Review error history for associated L-codes (L0, L1, etc.).
  • Check mains voltage stability and wiring.
  • Inspect the outdoor unit for blocked airflow or mechanical issues causing overload.

Actions:

  • Resolve underlying L-code causes before resetting.
  • If inverter trips recur, the drive module may need replacement.

Severity: Medium

Description: Fault on the room / internal air temperature sensor used for space heating control.

Checks:

  • Check the position of the room sensor or controller in the dwelling.
  • Inspect the cable for damage or dislodged plugs.
  • Measure sensor resistance and compare to specification.

Actions:

  • Relocate or replace the sensor as needed.
  • If using a third-party room thermostat, confirm wiring and settings.

Severity: High

Description: The outdoor DC fan has failed to run or is outside normal speed limits.

Checks:

  • Check that the fan rotates freely and is not obstructed by ice or debris.
  • Inspect fan connector and wiring at the outdoor PCB.
  • Look for signs of water ingress or burnt components on the fan or PCB.

Actions:

  • Replace the fan motor if it does not run when powered.
  • If a new fan does not resolve it, further diagnose the outdoor PCB or inverter.

Severity: High

Description: The supply voltage is outside the acceptable range for the unit.

Checks:

  • Measure line voltage at the unit terminals under load.
  • Check for undersized cable or long runs causing voltage drop.
  • Confirm there are no frequent brownouts or overvoltage events.

Actions:

  • Correct wiring or upgrade supply as required.
  • If voltage is within spec and the error continues, check the voltage sensing circuit on the PCB.

Severity: High

Description: The refrigerant pressure sensor signal is missing or out of range.

Checks:

  • Inspect the high-pressure sensor connection on the outdoor unit.
  • Check wiring for shorts, opens or corrosion.
  • Compare measured sensor output to expected values if equipment is available.

Actions:

  • Replace the pressure sensor if the signal is invalid.
  • If a new sensor does not help, the controller input may be defective.

Severity: Medium

Description: Fault on the second heating zone water outlet temperature sensor.

Checks:

  • Confirm that a second zone is actually used and wired.
  • Inspect sensor position on the zone 2 outlet pipe.
  • Check continuity of the sensor cable.

Actions:

  • Install or replace the zone 2 sensor as needed.
  • If unused, some controllers allow the input to be disabled in settings.

Severity: Medium

Description: Fault on the main water side heat exchanger outlet temperature sensor.

Checks:

  • Check sensor placement on the flow pipe leaving the unit.
  • Inspect wiring between sensor and hydronic PCB.
  • Measure resistance and compare with temperature.

Actions:

  • Replace the outlet sensor if defective.
  • Investigate the control board if the error persists with a good sensor.

Severity: Medium

Description: The unit has locked out after repeated PP protection events with very low outlet water temperature.

Checks:

  • Review system design for low return water temperatures (e.g. underfloor, large emitters).
  • Check for excessive flow or bypasses that may cause over-cooling.
  • Verify sensor readings for water inlet and outlet.

Actions:

  • Adjust flow rates and control settings to keep outlet within safe limits.
  • If problem persists, consult the system designer to review emitter sizing and hydraulics.

Severity: High

Description: The EEPROM associated with the refrigerant system or inverter module cannot be read correctly.

Checks:

  • Power the unit off fully and restart.
  • Check connectors on the inverter module and main PCB.
  • Verify there is no visible damage to memory devices on the board.

Actions:

  • If the error remains, the inverter module or associated PCB will likely need replacement.
  • Engage manufacturer technical support for board replacement procedures.

Severity: High

Description: H6 fan protection has occurred many times in a short period and the unit has locked out.

Checks:

  • Resolve root cause of H6 (fan or PCB fault) before resetting.
  • Check that the fan can run through several cycles without tripping.
  • Inspect for intermittent wiring or contact issues.

Actions:

  • After repairs, clear the error and test operation thoroughly.
  • If HH reappears, detailed diagnostics of the outdoor electronics are required.

Severity: High

Description: The system has seen repeated low-pressure protection events over a set time period.

Checks:

  • Check refrigerant charge and look for signs of leakage.
  • Verify water flow and air flow across the heat exchangers.
  • Inspect strainers, filters and fan operation.

Actions:

  • Have an F-gas engineer leak-test and recharge if necessary.
  • Address any flow issues before returning the unit to normal service.

Severity: High

Description: Refrigerant pressure has dropped below the minimum safe level.

Checks:

  • Check for insufficient load or very low water temperatures.
  • Inspect for signs of refrigerant leaks (oil stains, hissing, bubbles).
  • Verify that strainers and filters are clean and pumps/fans are operating.

Actions:

  • Do not keep resetting the unit – have an F-gas qualified engineer check the system.
  • Restore correct refrigerant charge and fix any leaks.

Severity: High

Description: Refrigerant pressure has exceeded the maximum safe level.

Checks:

  • Ensure outdoor coil and any air paths are clean and unobstructed.
  • Check that all water circuits are flowing and valves are open.
  • Verify that the system is not being run outside its specified temperature range.

Actions:

  • Clean coils and restore design water flow.
  • If pressures remain high, an engineer should check expansion valve operation and refrigerant charge.

Severity: High

Description: The compressor current has exceeded the allowed limit.

Checks:

  • Check mains voltage and phase balance (for three-phase models).
  • Listen for mechanical noises suggesting compressor mechanical problems.
  • Inspect wiring and contactors for overheating.

Actions:

  • Have an engineer measure running current and insulation resistance.
  • Replace compressor or inverter components if necessary.

Severity: High

Description: The compressor discharge temperature has risen above the protection threshold.

Checks:

  • Check outdoor airflow and ensure fans and coils are clean.
  • Verify correct water flow and leaving water temperature.
  • Check refrigerant charge and look for restrictions in the circuit.

Actions:

  • Correct any airflow or flow issues and reset the unit.
  • If overheating persists, a refrigeration engineer should investigate further.

Severity: High

Description: The temperature difference between water inlet and outlet is too large.

Checks:

  • Check water flow rate through the unit – a low flow will give a large temperature difference.
  • Verify all valves are open and strainers are clean.
  • Confirm the system is not blocked or air-locked.

Actions:

  • Increase flow rate by adjusting pump speed or valves.
  • Flush and balance the system if necessary.

Severity: High

Description: The inverter has detected an internal fault or overload condition.

Checks:

  • Check supply voltage and cabling.
  • Inspect outdoor PCB and inverter module for visible damage.
  • Look for associated L-codes that indicate the detailed cause.

Actions:

  • If supply and load conditions are normal, the inverter module may need replacement.
  • Contact an authorised service partner before replacing boards.

Severity: High

Description: General inverter module protection event.

Checks:

  • Review operating conditions when the fault occurred (ambient, load, mode).
  • Check supply voltage and wiring.
  • Inspect for blocked coils or seized fans that could overload the inverter.

Actions:

  • Address system-side causes (air/water flow, wiring).
  • If the inverter continues to trip, it may require replacement.

Severity: High

Description: The DC bus voltage is too low for safe inverter operation.

Checks:

  • Measure incoming mains voltage under load.
  • Check for loose terminals, undersized cable or long runs.
  • Inspect rectifier and DC link components for damage.

Actions:

  • Correct supply issues and retest.
  • If supply is sound, the inverter/rectifier section may need replacement.

Severity: High

Description: The DC bus voltage has risen above the safe limit.

Checks:

  • Check that the supply is not over-voltage.
  • Verify that power-factor and braking components are functioning correctly.
  • Confirm there are no wiring errors or incorrect connections.

Actions:

  • Have an electrician verify supply quality.
  • Replace damaged inverter components if over-voltage has occurred internally.

Severity: High

Description: Internal motor control (MCE) fault in the inverter drive.

Checks:

  • Power-cycle the unit and check if the error reoccurs immediately.
  • Inspect inverter PCB for signs of damage.
  • Confirm cooling of the inverter is adequate.

Actions:

  • If L4 repeats, the inverter module will usually need replacement.
  • Consult manufacturer technical support before replacing expensive boards.

Severity: High

Description: The inverter detects that the compressor speed is not increasing as commanded.

Checks:

  • Check for a seized compressor or mechanical blockage.
  • Verify correct wiring between inverter and compressor.
  • Listen for unusual noises or failure to start.

Actions:

  • Do not keep forcing restarts on a seized compressor.
  • Have a refrigeration engineer assess the compressor and inverter.

Severity: Medium

Description: Phase sequence or phase detection error linked to the inverter protection system.

Checks:

  • Confirm three-phase supply phase order is correct.
  • Check for loose or missing phases at the isolator or breaker.
  • Inspect wiring between terminals and inverter board.

Actions:

  • Correct any supply wiring issues.
  • If supply is correct, the inverter’s phase-detection circuitry may be faulty.

Severity: High

Description: The compressor frequency has changed too quickly, indicating instability or control issues.

Checks:

  • Review system settings for unrealistic capacity or curve settings.
  • Check supply voltage stability.
  • Inspect inverter and compressor connections.

Actions:

  • After confirming system conditions, replace the inverter if L8 persists.
  • Log conditions when the error occurs to aid diagnosis.